Control pressure of the system of fire protection with 3M Novec 1230 Fire Protection Fluid
The pressure operated switch of the system of fire protection with Novec 1230 Fire Protection Fluid is for the detection of a pressure drop in the system of balloon gas cylinders (view the Picture).
The pressure operated switch of a balloon gas cylinder can be installed for all balloon gas
cylinders with a capacity from 5 to 368 litres with a 2 or 3 inch (80 mm) outlet valve.
In case the pressure inside the balloon gas cylinder drops lower than 21 barg., the contacts of the switch will give alert signals to the control panel.
The pressure operated switch of the system of fire protection with Novec 1230 Fire Protection Fluid is for the detection of a pressure drop in the system of balloon gas cylinders (view the Picture).

In case the pressure inside the balloon gas cylinder drops lower than 21 barg., the contacts of the switch will give alert signals to the control panel.
Control pressure of the system of fire protection